Motor full load current

Typical efficiency and power factor fill in by motor size; change them to the nameplate values if you have them.

V
%

Result

Results appear here as you type.

Get this checked by an engineer

Indicative only. Rules, tariffs and site conditions vary; SKE engineers confirm the exact figures for approvals and designs.

Formula and basis

I = P(output) ÷ (√3 × V × η × PF) for three phase; I = P ÷ (V × η × PF) for single phase. Starting: DOL about 6 × FLC, star-delta about 2 to 2.5 ×, soft starter about 3 ×, VFD about 1.2 to 1.5 ×.

Electrical Load Calculation: how SKE helps

Questions

Why is my measured current lower than the full load current?

Most motors run below full load. Current falls with load, but power factor and efficiency also fall at light load.