Cables, earthing and protection

Cable size calculator

Gives the smallest XLPE cable that carries the current after derating and keeps the voltage drop within your limit. Defaults suit a Rajasthan summer (45 °C air, 30 °C ground).

V
m
°C
%

Result

Results appear here as you type.

Get this checked by an engineer

Indicative only. Rules, tariffs and site conditions vary; SKE engineers confirm the exact figures for approvals and designs.

Formula and basis

Current rating from IEC 60364-5-52 reference values for multicore XLPE (90 °C), method E (air) and D (ground), multiplied by temperature factor √((90 − T) ÷ (90 − Tref)) and grouping factor. Voltage drop = √3 × I × L × (R cos φ + X sin φ) with R at 90 °C and X = 0.08 Ω/km.

Electrical Drawing & Design: how SKE helps

Questions

Why does the calculator suggest a larger cable than my contractor?

Rajasthan air temperatures of 45 °C and grouped cables cut the current a cable can carry, and long runs need a bigger size for voltage drop. Maker catalogues often quote higher ratings at milder reference conditions; follow the maker's derating tables for the final selection.

What voltage drop is allowed?

Common practice is up to 3% for lighting and 5% for other loads from the supply point; motors also need a check on starting.