Cables, earthing and protection
Cable size calculator
Gives the smallest XLPE cable that carries the current after derating and keeps the voltage drop within your limit. Defaults suit a Rajasthan summer (45 °C air, 30 °C ground).
Result
Results appear here as you type.
Indicative only. Rules, tariffs and site conditions vary; SKE engineers confirm the exact figures for approvals and designs.
Formula and basis
Current rating from IEC 60364-5-52 reference values for multicore XLPE (90 °C), method E (air) and D (ground), multiplied by temperature factor √((90 − T) ÷ (90 − Tref)) and grouping factor. Voltage drop = √3 × I × L × (R cos φ + X sin φ) with R at 90 °C and X = 0.08 Ω/km.
Questions
Why does the calculator suggest a larger cable than my contractor?
Rajasthan air temperatures of 45 °C and grouped cables cut the current a cable can carry, and long runs need a bigger size for voltage drop. Maker catalogues often quote higher ratings at milder reference conditions; follow the maker's derating tables for the final selection.
What voltage drop is allowed?
Common practice is up to 3% for lighting and 5% for other loads from the supply point; motors also need a check on starting.