Fault level at the transformer secondary

Breakers and panels at the transformer must be rated for at least this fault level.

kVA
V
%

Result

Results appear here as you type.

Get this checked by an engineer

Indicative only. Rules, tariffs and site conditions vary; SKE engineers confirm the exact figures for approvals and designs.

Formula and basis

Full load current I = kVA × 1000 ÷ (√3 × V). Fault current Isc = I × 100 ÷ Z%. Ignores the source impedance, so it errs on the safe side.