- Fault level at the transformer secondary
Cables, earthing and protection
Fault level at the transformer secondary
Breakers and panels at the transformer must be rated for at least this fault level.
Result
Results appear here as you type.
Indicative only. Rules, tariffs and site conditions vary; SKE engineers confirm the exact figures for approvals and designs.
Formula and basis
Full load current I = kVA × 1000 ÷ (√3 × V). Fault current Isc = I × 100 ÷ Z%. Ignores the source impedance, so it errs on the safe side.