Conductor resistance at temperature

Useful for checking test readings and loop impedance.

mm²
m
°C

Result

Results appear here as you type.

Get this checked by an engineer

Indicative only. Rules, tariffs and site conditions vary; SKE engineers confirm the exact figures for approvals and designs.

Formula and basis

R = ρ20 × L ÷ A × (1 + α (T − 20)). ρ20: copper 0.017241, aluminium 0.028264 Ω·mm²/m; α: copper 0.00393, aluminium 0.00403.