- Home
- Calculators
- Connected load for a new LT connection (Rajasthan)
Load, tariff and equipment
Connected load for a new LT connection (Rajasthan)
Count the points and appliances. Ratings follow Annexure 1 of TCOS 2021; lights, fans, TV and plugs take a diversity (30% for domestic, 80% for others); other equipment counts at full rating.
Result
Results appear here as you type.
Indicative only. Rules, tariffs and site conditions vary; SKE engineers confirm the exact figures for approvals and designs.
Formula and basis
LED 15 W, tube 40 W, fan 60 W, light plug 60 W for each three or fewer, TV 100 W, power plug 500 W for each three or fewer, fridge 250 W, cooler 250 W, geyser 1500 W, AC 1500 / 2200 W, pump 360 W. Diversity on lights, fans, TV and plugs: domestic 30%, others 80%. Where both a geyser and an AC are installed, only the higher one counts. Supply type: up to 5 kW single or three phase; above 5 kW three phase LT up to 50 kVA demand; above 50 kVA HT 11 kV (TCOS 2021, clause 4.1).
Tariff source: RERC Tariff for Supply of Electricity 2025 (order dated 3.10.2025), Rajasthan DISCOMs.
Questions
Does fire-fighting equipment count in connected load?
No. TCOS 2021 Annexure 1 excludes fire protection equipment, and equipment not yet connected or kept as spares.