- Estimated design demand and transformer size (TCOS 7.5)
Load, tariff and equipment
Estimated design demand and transformer size (TCOS 7.5)
Used by the DISCOM for technical sanction of colonies, group housing and building complexes (TCOS 2021, clause 7.5(i)). Enter the areas that apply; leave the rest at zero.
Result
Results appear here as you type.
Indicative only. Rules, tariffs and site conditions vary; SKE engineers confirm the exact figures for approvals and designs.
Formula and basis
Domestic plots 1 kW, flats 4 kW, EWS/LIG 2 kW, non-domestic plots 4 kW, non-domestic built and resorts 5 kW, farm houses 2 kW, all per 1000 sq ft. Resort and farm house open areas add 25% of the built load. Industrial: 10 kW up to 1000 sq ft plus 5 kW for each further 1000 sq ft or part. Common facilities add 5% and miscellaneous 2%. kVA = kW ÷ 0.90. Lines and transformers are designed for 10% above this. Above 50 kVA: 11 kV supply with a transformer at the applicant's cost.
Tariff source: RERC Tariff for Supply of Electricity 2025 (order dated 3.10.2025), Rajasthan DISCOMs.
Questions
Can the developer declare a higher demand?
Yes. Where the developer indicates a higher demand, the higher figure is used (TCOS 2021, note to clause 7.5(i)).