Load, tariff and equipment
DG set size
A DG must carry the running load at 0.8 power factor and also take the largest motor starting with the rest running.
Result
Results appear here as you type.
Indicative only. Rules, tariffs and site conditions vary; SKE engineers confirm the exact figures for approvals and designs.
Formula and basis
Running kVA = kW ÷ 0.8. Motor starting kVA ≈ motor kW ÷ 0.85 ÷ 0.9 × starting multiple (DOL 6, star-delta 2.5, soft 3, VFD 1.5). The DG should handle about 1.5 × its rating briefly at start: required kVA = max(running kVA, (running kVA − motor kVA + starting kVA) ÷ 1.5), plus margin.
Tariff source: RERC Tariff for Supply of Electricity 2025 (order dated 3.10.2025), Rajasthan DISCOMs.