Load, tariff and equipment

DG set size

A DG must carry the running load at 0.8 power factor and also take the largest motor starting with the rest running.

kW
kW
%

Result

Results appear here as you type.

Get this checked by an engineer

Indicative only. Rules, tariffs and site conditions vary; SKE engineers confirm the exact figures for approvals and designs.

Formula and basis

Running kVA = kW ÷ 0.8. Motor starting kVA ≈ motor kW ÷ 0.85 ÷ 0.9 × starting multiple (DOL 6, star-delta 2.5, soft 3, VFD 1.5). The DG should handle about 1.5 × its rating briefly at start: required kVA = max(running kVA, (running kVA − motor kVA + starting kVA) ÷ 1.5), plus margin.

Tariff source: RERC Tariff for Supply of Electricity 2025 (order dated 3.10.2025), Rajasthan DISCOMs.